Subject: condenser approach temperature + help! gen. Помогите, пожалуйста, перевести!На русский. Energy Consumption A measure of the operation of the chiller is one good indication of ED 2000 performance We have a computer program that will estimate the cost of operating the chiller based on certain factors. A comparison of the condenser approach temperatures over the course of the cooling season can then be analyzed to determine energy savings. The following information should be collected: 1. Running Hours (derived from chiller panel) If there has been an increase in the condenser approach temperature over the course of a cooling season it is likely it is a result of fouling or a loss of refrigerant. A 1 increase in condenser approach may equate to a 1.5-3% increase in kW/ton and a subsequent increase in energy costs. If one would track the condenser approach temperature it should remain consistent over the course of a season. If it is not and it is a result of scale, the ED 2000 will maintain a consistent approach temperature. |
Спасибо! |
condenser approach temperature = температурный напор конденсатора |
You need to be logged in to post in the forum |