Subject: 3LEL.m Таблица Alarm PrioritiesPriority 1: Confirmed H2S Gas – 2ooN). Confirmed “High” HC Gas (25%, ***3LEL.m***) – 2ooN. Temporary Refuge Gas (H2S, HC, CO, CO2, O2). Confirmed Fire (Flame, Smoke, Heat) – voted or 1ooN. Fire suppression release (Deluge, CO2, etc.). MAC, GPA, Toxic Gas, PAPA. Critical System Faults. “Critical” Process (DCS) pre-alarms. Critical Loops (DCS). Field ESD Pushbuttons (ESD 1 &2). Правильно ли я понимаю, что это - трехкратное превышение нижней взрывоопасной концентрации? если так, что что значит буковка "m"? |
Не это ли? "Definitions of Terms Gas Concentration Measurement Terms used in this manual: • LEL: The volume ratio of flammable gas or vapor in air below which an explosive atmosphere will not be formed. • LEL.meter: Integral of the gas concentration along the optical path expressed in units of concentration, multiplied by the distance. NOTE: 100% LEL x 1 meter = 1 LEL.meter" http://media.msanet.com/na/usa/permanentinstruments/GasSensorsTransmitters/SafEyeXenon800/10055711.pdf |
You need to be logged in to post in the forum |