Hot Line Tag can be manually enabled by using a hotstick
to pull down the red manual handle, located on the front
of the recloser housing. When the HOT
LINE TAG handle is in the down position, all closing,
including reclosing and manual closing, is disabled.
The red LED is lit when Hot Line Tag is enabled.
When Hot Line Tag is active, protection shifts to one tripto-
lockout on the composite curve of the Hot Line Tag
definite time and the TCC1 curve, whichever is faster.
Hot Line Tag takes precedence over Cold Load Pickup,
and Fast Trips Disabled.

очень надеюсь на помощь специалистов. проблемы с частью "protection shifts to one tripto-lockout on the composite curve of the Hot Line Tag definite time and the TCC1 curve, whichever is faster". своего варианта не привожу , тк его попросту нет- данное предложение совершенно поставило меня в тупик :(
спасибо заранее за помощь

 october

link 25.08.2008 10:12 
срабатывание защиты происходит в точке "одно отключение = блокировка" на комбинированной характеристике

 Enote

link 25.08.2008 10:16 
protection shifts to one tripto-
lockout on the composite curve of the Hot Line Tag
definite time and the TCC1 curve
защита переключается на режим аварийного отключения в блокировку по составной (времятоковой) кривой с независимым временем срабатывания Hot Line Tag и времятоковой кривой ТСС1