Subject: 4,3 x In.
4,3 x In. - ?
3 x 377A - ?

With the given compressor torque the minimum tapping to guarantee a safe start is 85%. The starting current from the network is then reduced by a factor of 0,852. For a motor with 6 x In (Nominal Current) at start this means the network starting current is about 4,3 x In. Assuming a rated motor current of 521A this gives 2240A network current which is 200% of rated generator current (3 x 377A).

 Enote

link 4.09.2007 12:49 
написано
In (Nominal Current)
377A = 337 Ампер

 