link 13.03.2017 21:08 |
Subject: channels need to demand the safety function gen. Уважаемые коллеги, добрый вечер,прошу помочь с переводом сабжу, и, собственно, предложения ниже. During normal operation, both channels need to demand the safety function before it can take place. Это описание архитектуры 1oo2D This architecture consists of two channels connected in parallel. During normal operation, both channels need to demand the safety function before it can take place. In addition, if the diagnostic tests in either channel detect a fault then the output voting is adapted so that the overall output state then follows that given by the other channel. If the diagnostic tests find faults in both channels or a discrepancy that cannot be allocated to either channel, then the output goes to the safe state. In order to detect a discrepancy between the channels, either channel can determine the state of the other channel via a means independent of the other channel. Заранее благодарю. |
safety function исполняется только по запросу каналов |
|
link 13.03.2017 22:09 |
Спасибо, а к чему относится it can take place? |
Чтобы выполнить функцию, влияющую на безопасность, на неё должен поступить запрос от обоих каналов. |
before it can take place - прежде чем она (функция) будет исполнена |
|
link 14.03.2017 12:49 |
Благодарю! |