Subject: start flow guard
Z. Start flow guard

Safety equipment for refiner housing pressure
The safety system consists of two small pipes connected to the refiner housing. The pipes are purged with high pressure sealing water from the refiner. Each line is representing a limit in housing pressure (High and High-High). In each line there is a pressure switch, a purge meter and a flow guard.

The flow can be set with the hand valve (A) to correct value on the flow guard, approx 1 litre/minute. The alarm limit for the flow guards is 0.5 litre/minute and a flow under that limit interlocks the production on the refiner. This because there is not enough reliability in the control of the housing pressure when the flow is too low.