Subject: normal control switch trip помогите плиз перевести: normal control switch trip - ?The TLC trip is installed in parallel with the normal control switch trip (C.S./TRIP) and in series with the cutoff switch (CO./TLC). The auxiliary breaker trip circuit has been modified to allow the TLC to perform its proper functions when it is called upon to transfer automatically for a unit shutdown. Because the TLC will not proceed with a transfer unless it is allowed to trip the first breaker, the 86x/GEN and timer 2/GEN86 were added to the lockout circuit. The 86x relay is used to initiate a TLC transfer through the "Protective Relay Initiate" input to the TLC upon the trip of the 86/GEN relay. The timer allows the TLC to trip the auxiliary breaker and proceed with a controlled transfer. If under these conditions the TLC does not trip the auxiliary breaker, it is tripped through the 2/GEN 86 timer contact and drops the timer target (T). The timer contact also acts to block a TLC "protective relay initiated" transfer in the event of an 86/3us lockout trip. The TLC cutoff switch (CO./TLC) is wired to bypass the timer contact when the TLC is out of service. заранее спасибо
|